CATERPILLAR DIESEL GENERATOR 1460 KW OVERVIEW PART NAMES COMPLETE DETAIL WITH ENGLISH SUB TITLE

Published 2020-04-28
TECHNICAL DATA
Open Generator Set - - 1500rpm/50 Hz/400 Volts DM8367
Low Fuel Consumption
Generator Set Package Performance
Genset Power rating @ 0.8 pf
Genset Power rating with fan
1825 kVA
1460 ekW
Fuel Consumption
100% load with fan
75% load with fan
50% load with fan
382.8 L/hr 101.1 Gal/hr
292.1 L/hr 77.2 Gal/hr
209.8 L/hr 55.4 Gal/hr
Cooling System1
Air flow restriction (system)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity
0.12 kPa 0.48 in. water
398.0 L 105.1 gal
233.0 L 61.6 gal
165.0 L 43.6 gal
Inlet Air
Combustion air inlet flow rate 118.4 m³/min 4181.3 cfm
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)
488.2 º C 910.8 º F
305.1 m³/min 10774.5 cfm
203.2 mm 8.0 in
6.7 kPa 26.9 in. water
Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
953 kW 54197 Btu/min
1386 kW 78822 Btu/min
187 kW 10635 Btu/min
158 kW 8985 Btu/min
68.8 kW 3912.6 Btu/min
Alternator 2
Motor starting capability @ 30% voltage dip
Frame
Temperature Rise
4978 skVA
1625
125 º C 225 º F
Lube System
Sump refill with filter 401.3 L 106.0 gal
Emissions (Nominal) 3
NOx mg/nm3
CO mg/nm3
HC mg/nm3
7690.3 mg/nm³
324.3 mg/nm³
82.0 mg/nm³
1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2 UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator
temperature rise is based on a 40 degree C ambient per NEMA MG1-32.
3 Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values